6. EMS
Complete Initial installation first. This chapter covers the Schochman Engine Monitoring System (EMS). Complete its power, CAN, ECU and sensor wiring using the newest EMS installation manual. That manual supplies connector drawings, pinouts, electrical requirements and mounting instructions.
The EMS supports engine data from Rotax CAN and directly connected sensors, including ULS engine installations. Rotax 912 iS is the worked example in this chapter; it is not the only supported engine. Select sources and sensors for the equipment actually installed.
Perform configuration and calibration on the ground. Obtain operating limits from the applicable aircraft and engine documentation, and identify each sender and its measurement range before entering a calibration. A saved example is not an approved limit or a calibration for another aircraft.
For one display, perform the local checks below. With tandem displays, work from the PFD, keep both displays running during configuration, and complete the receiving-display restart and comparison at the end. Update the shared EMS once.
6.1. Confirm detection and update firmware
Open: MORE / SETTINGS / CONFIGURATION / HARDWARE.
Find EMS, labelled Schochman Engine Monitoring System. Confirm green ONLINE or a green SNxxxxxx serial. The EMS model is fixed in the current application; selecting its button does not choose a different EMS.
UI illustration: detected EMS. The serial and status are simulated.
Open: MORE / SETTINGS / UPDATES / DEVICES UPDATE. Use the EMS row. Internet access and login on the display are required to download an update.
Read the reported firmware v….
If an update is available, select UPDATE, then Update and Confirm in the two prompts. Communications stop temporarily; update on the ground.
Keep the EMS and display powered through download, upload and restart.
Wait for its returned firmware version and recheck HARDWARE detection. Upload complete – waiting for device restart is an intermediate state.
Complete firmware updating before collecting calibration samples.
UI illustrations: version numbers and progress are examples, not a release or installed-device confirmation.
Resistive calibration depends on the EMS firmware’s resistance conversion. Wait if the editor says Checking EMS firmware version. Calibration editing is unavailable. If it reports that firmware changed and recalibration is needed, recalibrate the affected resistive senders. If the mode changes while editing, discard pending changes and reopen the sensor as instructed. Do not copy an older resistance table into a new installation.
6.2. Plan the sources and sensor assignments
Open: MORE / SETTINGS / CONFIGURATION / EMS. Select a parameter to open its settings. ANALOG means a directly connected EMS input here; it also includes interrupt inputs, thermocouples and the shunt.
Parameter |
Source for the installation |
Additional setup |
|---|---|---|
Engine speed |
ROTAX_CAN or ANALOG |
Direct RPM uses the fixed interrupt input. |
Oil / manifold pressure |
ROTAX_CAN or ANALOG |
Direct inputs: voltage or current; select matching calibration. |
Oil / coolant temperature |
ROTAX_CAN or ANALOG |
Direct inputs: resistive sender and its calibration. |
EGT |
ROTAX_CAN or ANALOG |
Cylinder count; direct K-type inputs also have an EGT input-count setting. |
Fuel pressure 1 / 2 |
ANALOG |
Voltage, current or resistive type; configure each installed sender. |
Fuel quantity left / right / centre |
ANALOG for tank senders |
Resistive type; calibrate each tank independently in litres. |
Fuel flow |
ROTAX_CAN or ANALOG |
Direct flow needs the sensor’s pulses-per-litre factor. |
Shunt / main bus voltage |
Direct EMS measurement |
Match the shunt rating; primary bus voltage needs no calibration table. |
ECU voltages / manifold air temperature |
ROTAX_CAN |
Enable only applicable ECU indications. |
Lane indicator / throttle / ambient air temperature |
ROTAX_CAN |
Enable applicable indications; no custom calibration table. |
Lane hours display |
ROTAX_CAN or ANALOG |
ANALOG requires direct RPM as well for EMS-counted engine hours. |
A menu option does not establish that the chosen engine supplies that parameter. In particular, selecting ROTAX_CAN does not supply readings from an external tank or fuel-pressure sender. A pin must match the wiring, rather than merely the sensor’s default assignment.
MAIN BUS VOLTAGE 2: Leave it disabled. Contact Schochman support if you need this option.
6.2.1. An occupied pin
An occupied pin is shown differently in the list. On SAVE, an enabled direct sensor using that pin produces a Reassign / Cancel prompt. Reassigning removes the pin from its previous owner; it does not move a wire. A pin retained by a disabled sensor or a Rotax-source sensor can be released automatically. Recheck both affected parameters after any reassignment.
6.3. Use the common sensor controls
The left side sets the measurement. The right side contains CALIBRATION, NOTIFICATIONS and GRAPHICS, where applicable. Disabled fields are not required for the selected source or parameter.
UI illustration: Rotax-source settings. The reading and checkbox state are examples, not a pressure reference or a recommended compensation selection.
Set Enabled for an installed measurement. Disable absent optional measurements. Disabling also suppresses alerts from that source.
Select Source for this parameter. A mixed ECU/direct installation is normal; sources are selected per measurement.
For a direct sender, select its electrical Type, then the wired Pin. The list uses installation-manual labels such as D1-P10-RES and D2-P8-VOL, and filters for compatible electrical types.
Select a matching Calibration preset when available, or use Custom and enter the required curve. Do not use a preset only because its name looks similar. Some parameters have no selectable preset.
Review Smoothing. It is a time constant in seconds: zero disables the additional filter, and a larger value gives a steadier but slower response. Direct and Rotax sources retain separate smoothing values. Check response after changing it; do not copy a tank’s slow setting to engine warnings.
Select the SAVE under the sensor controls. Pending save replaces the live readings while measurement settings are unsaved. After saving, compare Value with the physical/reference measurement and Raw value with the sender signal where available. ECU raw readings show N/A.
DISCARD CHANGES restores the saved measurement settings. Leaving with unsaved changes offers DISCARD or STAY. The sensor SAVE is separate from the NOTIFICATIONS/GRAPHICS save controls; save both groups when both have changed.
6.4. Enter and check a custom calibration
For direct pressure and temperature senders, use the sender’s documented transfer curve or a suitable independent reference. Match units carefully: pressure is PSI, manifold pressure inHg, temperature °C and tank quantity L. Electrical inputs are shown in V, mA or ohm.
Select the direct source, type and pin first. Select Custom where a preset selector is available.
Open CALIBRATION. To replace a curve, use CLEAR and confirm. This clears pending points; it is not a saved replacement until sensor SAVE.
Select NEW SAMPLE and enter the known physical value. The pending row then shows a live electrical reading and a SET button.
Establish that reference value and let the signal settle. SET captures the current filtered electrical reading for it. Without a live EMS reading, a sample cannot be captured.
Repeat across the required measurement range. Alternatively, select a saved row’s physical or electrical value to enter a documented curve point. REMOVE deletes that pending point.
For a duplicate electrical input, choose KEEP EXISTING, USE NEW or RETRY. Retry the physical sample if the sender has not moved or settled; two volumes with the same electrical input do not define a usable segment.
Save with the sensor SAVE, reopen the parameter, and check reference values between calibration points as well as at them.
UI illustration: sample capture for a tank. All resistance readings are fictional; they are not a sender specification or the example aircraft’s calibration.
The application interpolates between curve points. Supply a curve covering the range to be measured; do not depend on endpoint behaviour to establish accuracy outside that range. Saving a table confirms storage, not measurement accuracy.
6.5. Configure pressures and temperatures
6.5.1. Fuel pressure 1 and 2
Configure each physically installed sender with ANALOG, its electrical type, its actual input and its own pressure calibration. Voltage, current and resistive calibrations are distinct; changing type does not make a different type’s curve correct. Leave an absent second sender disabled.
Verify the reading against the reference over the intended pressure range, then configure its display intervals and alerts. A fuel-pressure indication from a direct sender is independent of ECU CAN reception.
6.5.2. Oil and manifold pressure
For ECU-provided measurements use ROTAX_CAN. For a directly connected sender set Source to ANALOG, Type to VOLTAGE or CURRENT, and select the wired pin and a matching curve. Manifold calibration entries are in inHg, including decimal values; do not enter PSI or hPa values into that field.
Oil pressure also has Compensated. With Rotax CAN it selects the ECU’s compensated oil-pressure value. With an analog absolute-pressure sender, the current application subtracts AHRS ambient pressure, with negative results limited to zero; when ambient pressure is unavailable it retains the uncompensated value. Select this only for the installed sender/reference arrangement. Applying it to an already gauge-referenced sender would change the reference a second time. Confirm the result against the appropriate reference rather than using the checkbox to force a desired reading.
6.5.3. Oil and coolant temperature
Use ROTAX_CAN for ECU temperatures, or ANALOG / RESISTIVE with the installed sender’s curve and pin. Use its documented resistance/temperature values or compare against an independent temperature reference at several stable points. A plausible ambient reading alone does not verify the hot end of the curve. Do not heat or pressurize an installed engine system merely to produce a calibration point; use an appropriate sender/reference setup.
6.6. Calibrate fuel quantity
Configure FUEL QUANTITY LEFT, RIGHT and CENTER separately. Each enabled tank needs its own wiring assignment and calibration. Leave unused tanks disabled. Select ANALOG / RESISTIVE, then the actual pin.
UI illustration: left tank settings. Pin, litres and smoothing follow the saved example; Pending save is simulated. Choose the actual installation’s values.
6.6.1. Prepare a repeatable measurement
Use the aircraft’s fuel-handling procedure with the engine stopped. Position the aircraft level in the attitude specified for its fuel-quantity checks. If no attitude is specified, use a repeatable level ground attitude and record it with the calibration. A curve collected at one attitude does not establish accuracy at other attitudes or during manoeuvres.
Establish the tank’s empty reference and how unusable fuel is treated before starting. Record what the displayed litres represent. Do not label them usable fuel unless the chosen empty reference and the aircraft data support that interpretation. Keep the tank being calibrated isolated from transfers that would change its known volume.
Measure added fuel with a suitable calibrated measure. The number entered at each sample is the total quantity above the chosen empty reference, not the last increment poured in. Repeat the procedure for each tank; do not copy one tank’s electrical readings to another.
6.6.2. Recommended sample spacing
As a practical starting point, collect at least ten samples, including the empty and full reference points. For a 0–50 L calibration range, use 0, 5, 10, 15, 20, 25, 30, 35, 40, 45 and 50 L: eleven samples. Add more points near empty and wherever tank shape or sender movement makes the curve change rapidly. This is a sampling recommendation, not an accuracy guarantee or the capacity of the Rotax example aircraft.
In CALIBRATION, clear a curve being replaced and capture the empty-reference point at 0 L.
Add the first measured increment. Enter the resulting total with NEW SAMPLE. Let both the fuel surface and the filtered signal settle, then select SET.
Repeat up to the actual full reference. With slow smoothing, the electrical reading can continue moving after filling has stopped; wait for it to settle.
Inspect the table for mistaken totals, duplicate inputs, missing points and abrupt reversals. Correct the measurement or sender behaviour before saving.
Select sensor SAVE. A usable curve needs at least two distinct electrical inputs and two different volume values; that software minimum is not the recommended number of physical samples.
Reopen and check intermediate known quantities, particularly near empty, using the same attitude and settling conditions. If possible, check during a controlled reduction in quantity as well as filling. Record the differences; the acceptable error must come from the installation’s requirements.
Display unit offers Liters (L) and Percent (%). Calibration values remain litres. The highest calibrated volume defines 100% for that tank; a curve ending below the actual full quantity will therefore make that lower quantity appear full. Changing and saving the display unit on one tank updates the display unit for all three tank configurations, not just the selected tank. Check every enabled tank after this change.
Set any tank validity bounds only after understanding the indication at empty and full. A lower validity bound above the empty reading can make a low tank unavailable instead of producing its intended low-fuel alert.
6.7. Configure fuel flow
For ECU flow, select ROTAX_CAN. For a directly connected pulse sensor, select ANALOG. Its input is fixed at D1-P18-INT (shown as DSUB_25_P18 in the software); it is not assigned from the general analog-pin list.
UI illustration: direct fuel-flow setup awaiting a sensor factor. It is not the worked Rotax example’s ECU-source selection.
Select Set pulses/L and enter the positive pulses-per-litre value from the installed sensor’s calibration information. Convert a factor specified per another volume unit before entry.
Select sensor SAVE. The displayed flow is calculated as pulses per minute multiplied by 60 and divided by pulses per litre.
Compare accumulated indicated consumption with an independently measured consumed quantity over a suitable ground check. Confirm that the sensor measures engine consumption; this setting does not subtract a second return-flow sensor.
Recheck low and normal flow, the stopped-flow indication and the effect of smoothing. Correct a wrong factor or measurement arrangement before relying on calculated consumption.
Tank quantity and the fuel manager’s remaining/used fuel are separate. The latter is a running calculation that needs a correct initial remaining quantity and valid consumption data; calibrating tank senders does not set it. The fuel manager is not a replacement for the individual tank checks. Routine refuelling and remaining/used-fuel operation are outside this configuration procedure.
6.8. Configure RPM and engine hours
For the Rotax 912 iS example, select ROTAX_CAN for ENGINE SPEED and LANE HOURS DISPLAY. Verify RPM and both lane-hour values against the engine’s available reference information.
For direct RPM, select ANALOG. The fixed input is D2-P25-INT (shown as DSUB_37_P25 in the software). The current implementation treats one input pulse per revolution as RPM; there is no user pulses-per-revolution or gearbox-ratio control. Confirm the pickup’s pulse relationship and compare actual engine RPM with an independent reference before accepting the indication. Do not compensate for a mismatch with display intervals or smoothing.
For EMS-counted hours, both ENGINE SPEED and LANE HOURS DISPLAY must be enabled and set to ANALOG. The EMS then counts time above 100 RPM and stores it in the EMS itself. A new counter starts at zero; it does not import the engine’s prior service hours, and the UI has no initial-hours entry. The counter is saved periodically and after a detected stop, so verify normal shutdown persistence rather than treating a forced power loss as a full save.
Keep ECU lane hours and EMS-counted running hours distinct in the aircraft’s records. Display configuration backup does not recreate a counter stored in a replacement EMS.
6.9. Configure exhaust gas temperatures
For the Rotax example, select ROTAX_CAN and Cylinders: 4. The reviewed ECU path supplies up to four EGT channels.
For direct K-type probes, use ANALOG and K-TYPE calibration. Set Cylinders to the engine’s actual cylinder count and EGT inputs to 4 or 6 for the input bank being used. These are separate controls; selecting six inputs does not mean the engine has six cylinders. The EMS supports six direct thermocouple inputs.
UI illustration: the direct-input controls, not the Rotax example’s selected data source. Readings are simulated as unavailable.
Check the individual probe responses and their cylinder identification. The settings Value field can list six direct temperatures; the cockpit’s individual EGT sliders currently cover channels 1–4. Do not treat those four sliders as verification of inputs 5 and 6.
6.10. Configure electrical and remaining ECU indications
6.10.1. Shunt and primary bus voltage
Open SHUNT and match Shunt type to the installed shunt’s rated current and voltage drop. For example, 50 A / 50 mV is a particular shunt resistance; another 50 mV shunt with a different current rating needs its own selection. Source and pin are fixed; there is no custom calibration table.
UI illustration: shunt rating and smoothing from the saved example. Zero current is synthetic, not a zero-offset calibration.
Save, then compare the current’s magnitude and sign with an independent measurement under known loads. Confirm what the shunt location measures in this aircraft. It is not automatically the sum of every electrical load.
Enable MAIN BUS VOLTAGE and compare it with a meter at the relevant supply point. This is the EMS’s direct voltage measurement; it has no user pin or custom curve. Set its graphics and alerts for the actual electrical system. Shunt red-interval notification controls are disabled in the current editor; do not assume it provides a configurable shunt alarm.
6.10.2. ECU indications
For the Rotax example, enable applicable ECU-A VOLTAGE, ECU-B VOLTAGE, MANIFOLD AIR TEMP, LANE INDICATOR, THROTTLE POSITION and AMBIENT AIR TEMP indications. These have fixed ECU sources and no sender calibration table. Enablement and the availability of smoothing, graphics and notifications vary by indication; a disabled tab does not call for a fabricated calibration.
Verify lane A and B reception independently using the engine’s normal ground check procedure. EMS ONLINE alone does not establish reception from both ECU lanes or the validity of every ECU parameter. Resolve missing lane or engine data before accepting the corresponding indications.
6.11. Set graphics, validity bounds and alerts
6.11.1. Graphics intervals
Open the parameter’s GRAPHICS tab. The colour rows describe the existing dial or slider intervals. Enter each required Min / Max boundary in the displayed measurement unit, maintaining an ordered sequence. Adjacent rows share boundaries. The editor adjusts boundaries of existing intervals; it does not provide a general colour or interval-count selector.
UI illustration: GRAPHICS interval-table crop. Boundaries follow the saved example and are not approved limits for another engine. The OpenGL instrument preview and save controls are outside this crop.
Interval edits preview on the instrument before saving. Select SAVE in GRAPHICS to persist them; DISCARD restores saved intervals. Review the NOTIFICATIONS settings before saving: its validity/alert edits share this save group with GRAPHICS. The preview checks appearance, not wiring, calibration or alarm delivery.
6.11.2. Notifications and valid data
Open NOTIFICATIONS. For direct sources, optional MIN / MAX validity bounds determine whether a measured value is considered usable. Enter these in the displayed engineering unit, not the sender’s raw V/mA/ohm units.
UI illustration: independent validity and red-interval alert controls. The selections are illustrative, not a recommended low-fuel policy.
Validity bounds are not operating-warning thresholds. A reading outside them becomes unavailable and does not produce the normal red-interval alert. Keep genuine low/high operating conditions inside the valid measurement range; use GRAPHICS intervals for their warning bands. A display showing unavailable data is not confirming a safe engine condition.
Under In RED interval, choose Audible alert and Flashing indicator as required for that instrument. Their states are separate; disabling sound does not disable flashing. A red colour band alone does not prove that either notification is enabled. These controls concern red intervals, not every yellow caution or every ECU lane warning.
Select the tab’s SAVE, reopen both tabs and verify every boundary and alert selection. Check the live indication, audible path and visual warning during an appropriate ground check. Use a controlled reference or test input when available; do not exceed an engine limit to trigger a warning. Do not treat absent sound with unavailable data as an alarm-system test.
6.12. Rotax 912 iS worked example
This example combines ECU engine data with direct tank senders and a shunt. The tank and shunt entries below are recorded example settings; configure and verify the ECU source arrangement using the preceding procedures. This is not a complete transferable profile.
Item |
Example configuration |
|---|---|
ECU engine measurements |
ROTAX_CAN for RPM, oil/manifold pressure, oil/coolant temperature, four-cylinder EGT, fuel flow and applicable ECU indications. |
Left fuel tank |
Enabled, ANALOG / RESISTIVE, D1-P10-RES, Liters (L), smoothing 20 s. |
Right fuel tank |
Enabled, ANALOG / RESISTIVE, D1-P13-RES, Liters (L), smoothing 20 s. |
Centre tank |
Disabled in the saved example. |
Tank sample volumes |
Each saved curve has ten points: 0, 4, 8, 12, 16, 20, 24, 28, 32 and 36 L. |
Shunt |
Enabled, 50 A / 50 mV, smoothing 1 s. |
External fuel pressure |
Configure the physically installed sender using its actual type, pin and calibration; these sender details are not specified in this example. |
36 L is the highest recorded tank sample, not a verified tank capacity. Confirm the full range before accepting the percentage or litres indication.
The saved resistance tables are not reproduced: calibration curves must be compatible with the installed EMS firmware. Collect fresh samples for the installed senders as described above. Similarly, confirm all graphic boundaries and alert states against the aircraft’s current documentation instead of copying the example’s numbers.
6.13. Save, restart and verify the installation
Save the sensor group and NOTIFICATIONS/GRAPHICS group for every changed parameter. Resolve any Failed to save settings, pin-release or component-range save failure before continuing. Reopen and confirm the final settings; do not assume a failed multi-setting save rolled back everything already written or previewed.
On the configuring display, check every enabled measurement against its reference and confirm absent equipment is disabled. Complete the intended normal, low/high, unavailable-data and warning checks.
Restart the application on the ground and confirm settings and readings persist. A fresh reading after restart is required, not just a remembered dial position.
With tandem displays, wait for configuration delivery. The receiving display reports EMS configuration synchronized. Restart EFIS to apply it. Received EMS settings and graphics are saved for restart; the existing running indication is not proof they have been applied.
Restart the receiving application, then compare both displays’ sources, enablement, pins, calibration points, smoothing, units, intervals and alert selections. Check every enabled tank, not only the one last edited.
Verify actual received readings and the required warnings on both displays, and recheck the originating display. Successful saving or a synchronization popup alone does not establish correct tandem operation.
Settings are stored on the displays; the EMS owns its direct-input engine-hour counter. Display configuration profiles include sensor/graphics settings, but are not a substitute for verifying a restored installation, its hardware or that hour counter. Keep the calibration references, aircraft attitude, sample record, software/firmware versions and completed checks with the installation record.
6.14. Diagnose missing or unexpected readings
Open: MORE / SETTINGS / DIAGNOSTICS / EMS for EMS reception, and … / ENGINE for the engine-data path.
UI illustration: reception status. It does not verify calibration or ECU lanes.
Observation |
Check |
|---|---|
EMS OFFLINE |
Power and system CAN installation, followed by HARDWARE and EMS diagnostics. |
EMS ONLINE, ECU data missing |
Engine power, the separate ECU A/B connections and ENGINE status. Then check the affected parameter’s source and enabled state. |
Pending save |
Save or discard sensor edits. The displayed value is not a preview of an unsaved measurement configuration. |
Missing direct reading |
Enabled state, actual wire/pin, electrical type, compatible calibration, validity bounds and fresh reception. An unused pin or incompatible curve cannot be repaired by changing graphic intervals. |
Wrong tank quantity or premature 100% |
Known volume/reference attitude, sender settling, the complete individual tank curve and its highest recorded volume. Check the shared display unit. |
Fuel-flow setup will not save |
A direct enabled flow sensor requires a positive pulses-per-litre factor. |
Invalid fuel calibration |
Repair invalid/duplicate/missing points or clear and re-enter the curve; save and check it again before use. |
Calibration blocked after update |
Allow firmware identification to finish; follow the editor’s discard/reopen message and recalibrate incompatible resistive curves. |
Values correct but warning missing |
Data availability, source enablement, red intervals, separate audible/flashing selections, successful save and the physical audio/visual check. |
Other display still uses old settings |
Ethernet configuration sharing, received restart prompt, successful restart and direct field-by-field comparison on both displays. |